BURNER FLAME CONTROL
5 SERIES
page 4 di 5
DOUBLE / SINGLE ELECTRODE FLAME DETECTION
IN ACCORDANCE WITH STANDARD EN 298
On CF5 it is possible to set some
functions and some values through 8
microswitches housed on the on-board
electronic board.
The basic configuration of
microswitches is all 0
TIMES SETTINGS .
Pre Purge Time setting
Pre Purge 5 sec
Pre Purge 1 sec
Pre Purge 8 sec
Pre Purge 10 sec
Pre Purge 20 sec
Pre Purge 30 sec
Pre Purge 50 sec
Pre Purge 70 sec
Ignition Time setting
Ignition Time 5 sec
Ignition Time 12 sec
Safety Time loss of Flame
Safety Time 2 sec
Safety Time 3 sec
FUNCTIONS SETTINGS .
Attempt to re-ignite after loss of flame
Yes
No
Ignition/re-ignitio attemps numbers
N° 1
N° 3
Detection flame circuit 24h self check
Enabled
Disabled
Self check OK
Self check No flame detection
Self check No flame detection