4.11
External AC Circuit
Breaker and Residual
Current Device
Please install a circuit breaker to ensure the inveer is able to disconnect
from grid safely. The inveer is integrated with a RCMU, however, an
external RCD is needed to protect the system from tripping, either type A
or type B RCD are compatible with the inveer.
The integrated leakage current detector of inveer is able to detect the
real time external current leakage. When a leakage current detected
exceeds the limitation, the inveer will be disconnected from grid quickly,
if an external residual current device is connected, the action current
should be 30mA or higher.
Caution:For safety operation and regulation compliance, it is requested to install
a breaker (32A) between grid and inveer.
3029
CT wire Corresponding po in meter
IA (white) 13
iA (blue) 14
IB (white) 16
IB (blue) 17
IC (white) 19
IC (blue) 21