Installation
100
Install horizontally.
Indoor unit
Be horizontal
Flexible hose
Max. allowable axis gap.
Indoor unit
Max. 20 mm
Max. allowable bending angle.
Max. 30˚
Indoor unit
NOTE
If a concentrated drain pipe is installed, refer to the figure below.
Air ventilation
Concentrated
drain pipe
1/100 or more slope100 mm or more
Connecting the power and communication cables
CAUTION
Always remember to connect the air conditioner to the grounding system
before performing the electric connections. Use a crimp ring terminal at
the end of each wire.
The indoor unit is powered through the outdoor unit by means of a H07
RN-F connection cable (or a more power model), with insulation in synthetic
rubber and a jacket in polychloroprene (neoprene), in accordance with the
requirements specified in the standard EN 60335-2-40.
1 Remove the screw on the electrical component box and remove the
cover plate.
2 Route the connection cord through the side of the indoor unit and
connect the cable to the terminals refer to the figure below.
3 Route the other end of the cable to the outdoor unit through the ceiling &
the hole on the wall.
4 Reassemble the electrical component box cover, carefully tightening the
screw.
F1
F2
V2
F3 F4
V1
F1 F2
1(L) 2(N)
N
L
1(L) 2(N)
2
1
Indoor Unit
Cable
clamp
Indoor
Power
Main power
cable
Communication
cable
Indoor power supply
Power supply Max/Min(V) Indoor power cable
220 to 240V, 50 Hz
±10%
1.5 mm² ↑, 3 wires
Communication cable
0.75 to 1.5 mm², 2 wires