EasyManua.ls Logo

Samsung AC MN KH/EU Series - Page 112

Samsung AC MN KH/EU Series
117 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
112
Items Maximum allowable length
Outdoor unit models
AC090MXADKH
AC100MXADKH
AC100MXADNH
AC120MXADKH
AC120MXADNH
AC140MXADKH
AC140MXADNH
Main pipe (L1) 50 m 75 m
Max. height difference
between outdoor and
indoor units (h1)
30 m 30 m
L1
h
1
n=1
indoor
Outdoor
Temper grade and minimum thickness of the refrigerant pipe
Outer diameter [mm] Minimum thickness [mm] Temper grade
ø6.35 0.7
C1220T-O
ø9.52 0.7
ø12.70 0.8
ø15.88 1.0
ø15.88 0.8
C1220T-1/2H OR
C1220T-H
ø19.05 0.9
ø22.23 0.9
CAUTION
Be sure to use C1220T-1/2H (Semi-hard) pipe for more than Ø19.05 mm.
If you use C1220T-O (Soft) pipe for Ø19.05 mm, the pipe may be broken,
which can result in an injury.
Make at least one round:
It will reduce noise and vibration
The appearance of the unit may be different from the diagram depending
on the model.
CAUTION
After connecting the pipes with knock-out treatment, plug the space
around the pipes.
After connecting the pipes, proceed exactly as directed in the guide to
prevent interference with the internal parts.

Related product manuals