27
Installation Procedure
Setting the installation options in a batch
Installation option No. for an indoor unit address: 02XXXX-1XXXXX-2XXXXX-3XXXXX
1 Make sure that the power is supplied to the
indoor unit. If the indoor unit is not plugged in, it
must include a power supply.
F1
1(L)
2(N)
F2
V1
V2
F3
F4
Indoor Unit
2 Set the installation options of indoor units, by referring to the following table and by following the steps in Common
steps for setting the addresses and options on page 18.
• The installation options of indoor units are set to like a below table by default.
Model
AC026RNNDKG
AC035RNNDKG
AC052RNNDKG
AC071RNNDKG
Installation option 020000-100001-200000-300000 020000-100031-200000-300000
• The SEG20 option, Individual control with remote control, allows you to control multiple indoor units individually
by using the remote control.
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Function Page Mode
Reserved
Use of external
temperature sensor
Use of central control
Compensation of the
fan RPM
Indication
and details
Indication Details Indication Details Indication Details Indication Details Indication Details
0 2
0 Disuse 0 Disuse 0 Disuse
1 Use 1 Use 1
High ceiling
mode
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Function Page Use of drain pump
Reserved Reserved
Compensation of the wind-free fan RPM
Dew removal operation
in Wind-Free mode
Indication
and details
Indication Details Indication Details Indication Details Indication Details
1
0 Disuse Model
AC026RNNDKG
AC035RNNDKG
AC052RNNDKG
AC071RNNDKG
0
Maintain
blade
status in
Wind-Free
mode
1 Use
0
Default
3step↑
1 1step↓ 2step↑
1
(Default)
Cooling
operation
by opening
the blade
2
Use with 3
minute delay
2
2step↓ 1step↑
3 3step↓
Default
CAC R-32_Mini 4way_IM_DB68-08129A-00_EN_20181115.indd 27 2018/11/15 13:49:33