Outdoor units
2. Summary Table
Capacity
(Btu/h)
Model Code
Net Size
(WxHxD inch)
Net Weight
(lbs)
Airow
(CFM)
Sound Pressure Level
(dBA)
Sound Power
Level (dBA)
Cooling Heating
30,000 CXH24UPB (AC024BXUPCH/AA) 37 x 39-5/16 x 12-1 163 2,684 50 52 70
40,000 CXH36UDB (AC036BXUDCH/AA) 37 x 39-5/16 x 12-1 172 2,684 53 55 73
45,000 CXH36UPB (AC036BXUPCH/AA) 37 x 47-5/8 x 12-1 196 3,531 52 54 73
55,000 CXH48UPB (AC048BXUPCH/AA) 37 x 47-5/8 x 12-1 196 3,531 55 57 75
59,000 CXH60UPB (AC060BXUPCH/AA) 37 x 55-7/8 x 12-1 223 4,414 56 58 75
Model Outdoor Unit Input Current (Amperes) Power Supply
Outdoor Unit
Rated Voltage range Outdoor Unit
MCA(A) MOP(A)
Hz Volts Min. Max Cooling Heating
CXH24UPB (AC024BXUPCH/AA) 60 208-230 187 253 11.3 11.5 24.1 30
CXH36UDB (AC036BXUDCH/AA) 60 208-230 187 253 18.0 14.5 24.4 35
CXH36UPB (AC036BXUPCH/AA) 60 208-230 187 253 15.6 15.1 25.6 35
CXH48UPB (AC048BXUPCH/AA) 60 208-230 187 253 24.8 22.2 32.7 40
CXH60UPB (AC060BXUPCH/AA) 60 208-230 187 253 29.8 26.3 33.2 40
Performance Characteristics
Electric Characteristics
• Sound data is based on cooling operation.
• MCA : Minimum circuit amperes (A)
• MOP: Maximum Overcurrent Protective Device (A)
• Select wire size based on the value of MCA.