Outdoor Units
8. Capacity Correction
Pipe Length (ft)
24.6 45 60 75 90 100
Level Difference (ft)
49 0.95 0.94 0.93
45 0.96 0.95 0.94 0.93
30 0.97 0.97 0.96 0.95 0.94
15 0.99 0.98 0.97 0.97 0.96 0.95
0 1.00 0.99 0.98 0.98 0.97 0.96
-15 1.00 1.00 0.99 0.98 0.98 0.97
-30 1.00 1.00 0.99 0.99 0.98
-45 1.00 1.00 0.99 0.99
-49 1.00 1.00 0.99
Pipe Length (ft)
24.6 45 60 75 90 100
Level Difference (ft)
49 1.00 1.00 1.00
45 1.00 1.00 1.00 1.00
30 1.00 1.00 1.00 1.00 1.00
15 1.00 1.00 1.00 1.00 1.00 1.00
0 1.00 1.00 1.00 1.00 1.00 1.00
-15 0.99 0.99 0.99 0.99 0.99 0.99
-30 0.99 0.99 0.99 0.98 0.98
-45 0.98 0.98 0.98 0.98
-49 0.98 0.98 0.98
Cooling
Heating
ꞏ CXH60UPB (AC060BXUPCH/AA)