4-16 Samsung Electronics
Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation PAGE MODE
RESERVED
Use of external
temperature
sensor
Use of central control
RESERVED
Indication and
Details
Indication Details Indication Details Indication Details Indication Details
02
0 Disuse 0 Disuse
1 Use 1 Use
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Explanation PAGE Use of drain pump Use of Hot Coil
Use of Electric
Heater
RESERVED
Master / Slave
Indication and
Details
Indication Details Indication Details Indication Details Indication Details
Indication Details
1
0 Disuse 0 Disuse 0 Disuse
0 slave
1 Use 1 Use 1 Use
1 master
2
Use +
3minute
delay
---- --
Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
Explanation PAGE Use of external control
Setting the output of
external control
S-Plasma ion Buzzer control
Number of hours
using filter
Indication and
Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
2
0 Disuse 0 Thermo on 0 Disuse 0
Use of
buzzer
2 1000 Hour
1
ON/OFF
Control
1 Operation on
1
Use 1
Non use of
buzzer
6 2000 Hour
2
OFF
Control
3
WINDOW
ON/OFF
Control
Option SEG19 SEG20 SEG21 SEG22 SEG23 -
Explanation PAGE
control of a remote
controller
Heating setting
compensation
RESERVED
Away Set OFF
Timer
-
Indication and
Details
Indication Details Indication Details Indication Details Indication Details -
3
0 or 1 Indoor 1 0 Disuse 0 or 1
Auto Set OFF
30Min.
-
2 Indoor 2 1 2°C 2
Auto Set OFF
60Min.
3 Indoor 3
2 5°C
3
Auto Set OFF
120Min.
4 Indoor 4 4
Auto Set OFF
180Min.
5. Press the button to save and complete the option setting.
6. Press the
button to exit to normal mode.
t Press button anytime during setup to exit without setting.
t Option code will not be applied if you don't press
button.
t Setting Installation option code is available only with a master wired remote controller.
t Setting Installation option code is available when there is one on one connection between a wired
remote controller and an indoor unit.
NOTE