Performing leak tests
LEAK TEST WITH NITROGEN (before opening valves)
In order to detect basic refrigerant leaks, before recreating the vacuum and
recirculating the R-410A, it’s responsible of installer to pressurize the whole
system with nitrogen (using a cylinder with pressure reducer) at a pressure
above 40 bar (gauge).
LEAK TEST WITH R-410A (after opening valves)
Before opening valves, discharge all the nitrogen into the system and create
vacuum. After opening valves check leaks using a leak detector for refrigerant
R-410A.
Once you have completed all the connections, check for possible leaks using
leak detector specically designed for HFC refrigerants.
A(Gas)
A(Gas)
B(Liquid)
The designs and shape are subject to
change according to the model.
To check for gas leaks on the
Outdoor unit
Then, using a leak detector, check the
Valves on sections A and B.
02 INSTALLATION