Dimension and weight
Type Model Net dimension (WxDxH) (mm) Net weight(kg)
Outdoor Unit
AC026HCADKH 720*265*548 29.5
AC035HCADKH 720*265*548 29.5
AC052HCADKH 880*310*638 45.0
AC060HCADKH 880*310*793 55.0
AC071HCADKH 880*310*793 55.0
AC052HCAPKH 880*310*793 54.0
Model specication (
Dimension and weight)
Appendix
No. Meaning Remarks Error Code
29 EEV or Valve Close error-Self diagnosis
1. Check if the service valve is open
2. Check for refrigerant leakage (pipe connections,
heat exchanger) and charge refrigerant if
necessary
3. Check if there's any blockage on refrigerant
cycle (indoor unit/outdoor unit)
4. Check if additional refrigerant has been added
after pipe extension
E422
30 Outdoor EEPROM checksum error between MAIN and INVERTER.
Check Outdoor Inverter PBA
E590