4-20 Samsung Electronics
4-3-6 VIRUS DOCTOR(Micro PlasmaIon) error
Measure the amount of Ion with tester.
No
Yes
Is VIRUS DOCTOR Connector
disconnected from the PCB?
Resume operation using ion counter
after connecting to the
connector PCB
Indoor unit display
(VIRUS DOCTOR) X(Fan) X(Reservation) X(Defrost) X(Operation)
Criteria
VIRUS DOCTOR non-operation
Cause of problem
Check for VIRUS DOCTOR connector disconnect
On
Flickering
X
Off
T
he
number
of
measured
I
on
Is
more
Than
100,000.
Change the VIRUS DOCTOR Kit
(it’s out of the work)
Normal operation
Yes
VIRUS DOCTOR Kit
Tester: ITC201A