17
English
Installation Procedure
Outdoor-to-indoor power and communication
cables specifications
Indoor unit :
1WAY CST(AC***BN1***)
360CST(AC***BN6***)
4WAY CST(AC***BN4***)
Mini4way CST(AC***BNN***)
Console(AC***BNJ***)
RAC(AC***BNT***, AC***BNA***)
Indoor power supply
Power supply Max/Min (V) Indoor power cable
, 208-230V~, 60Hz ±10%
0.0012 inch²↑
(0.75mm2 ↑), 3 wires
Communication cable
0.0012 inch²↑ (0.75mm2 ↑), 2 wires
Indoor unit :
Duct(AC***BNL***, AC***BNH***)
Indoor power supply
Power supply Max/Min (V) Indoor power cable
, 208-230V~, 60Hz ±10%
0.0023 inch2 ↑
(1.5mm2 ↑), 3 wires
Communication cable
0.0012 inch²↑ (0.75mm2 ↑), 2 wires
Indoor unit :
MPAH(AC***BNZ***)
Indoor power supply
Power supply Max/Min (V) Indoor power cable
, 208-230V~, 60Hz ±10%
0.0039 inch2 ↑
(2.5mm2 ↑), 3 wires
Communication cable
0.0012 inch²↑ (0.75mm2 ↑), 2 wires
Power supply cords of parts of appliances for outdoor
use shall not be lighter than polychloroprene sheathed
flexible cord. (Code designation IEC:60245 IEC 57 /
CENELEC: H05RN-F)
When installing the indoor unit in a computer room or
network room, use the double shielded (tape aluminum /
polyester braid + copper ) cable of FROHH2R type.
Step 5 Optional: Extending the
power cable
1 Prepare the following tools.
Tools Spec Shape
Crimping pliers MH-14
Connection sleeve
[Inch(mm)]
0.78 (20)x
Ø0.25 (6.5) (HxOD)
Insulation tape Width 19 mm
Contraction tube
[Inch(mm)]
2.75 (70)x
Ø0.31 (8.0) (LxOD)
2 As shown in the figure, peel off the shields from the
rubber and wire of the power cable.
Peel off 0.79 inch (20 mm) of cable shields from the
pre-installed tube.
Power cable
[Unit : inch(mm)]
0.79
(20)
0.79
(20)
0.79
(20)
2.36
(60)
4.72
(120)
7.0 9
(180)
7.0 9
(180)
4.72
(120)
2.36
(60)
0.79
(20)
0.79
(20)
0.79
(20)
Pre-installed
tube for the
power cable
CAUTION
For information about the power cable specifications
for indoor and outdoor units, refer to the installation
manual.
After peeling off cable wires from the pre-installed
tube, insert a contraction tube.