Connecting the cable
Power Cable Specications
f The power cable is not supplied with air conditioner.
- Select the power supply cable in accordance with relevant local and national regulations.
- Wire size must comply with the applicable local and national code.
- Specications for local wiring power cord and branch wiring are in compliance with local cord.
Type
Model
Power
source
RLA (A)
FLA
MCA MOP
Outdoor Unit Indoor Unit
Outdoor Unit Indoor Unit
FAN1 (A) FAN2 (A) FAN1 (A) FAN2 (A)
A
AC024JXADCH/AA
AC024JN4DCH/AA
208~230 V /
60 Hz
9.00
0.48 0.33 12.06 20
AC024KN4DCH/AA 0.48 0.33 12.06 20
AC024JNHDCH/AA 0.48 0.85 12.58 20
AC024KNZDCH/AA 0.48 1.85 13.58 20
AC024MNHDCH/AA 0.48
1.5 13.5 20
AC024MNADCH/AA 0.48 0.7 12.5 20
AC030JXADCH/AA
AC030JN4DCH/AA
15.10
0.48 0.35 19.705 30
AC030KN4DCH/AA 0.48 0.35 19.705 30
AC030JNHDCH/AA 0.48 1.9 1.9 23.155 35
AC030KNZDCH/AA 0.48 2.35 21.71 35
AC030MNHDCH/AA 0.48 1.5 1.5 23 35
AC030MNTDCH/AA 0.48 0.9 20.3 30
B
AC036JXADCH/AA
AC036JN4DCH/AA
17.00
0.48 0.48 0.35 22.08 35
AC036KN4DCH/AA 0.48 0.48 0.35 22.08 35
AC036JNHDCH/AA 0.48 0.48 1.9 1.9 25.53 40
AC036KNZDCH/AA 0.48 0.48 4.15 26.36 40
AC036MNHDCH/AA 0.48 0.48
2
2
26.5 40
AC036MNTDCH/AA 0.48 0.48 0.9 23.2 35
AC042JXADCH/AA
AC042JN4DCH/AA
17.00
0.48 0.48 0.35 22.08 35
AC042KN4DCH/AA 0.48 0.48 0.35 22.08 35
AC042JNHDCH/AA 0.48 0.48 1.9 1.9 25.53 40
AC042KNZDCH/AA 0.48 0.48 4.15 26.36 40
AC042MNHDCH/AA 0.48 0.48
2
2
26.5 40
AC048JXADCH/AA
AC048JN4DCH/AA
17.00
0.48 0.48 0.35 22.08 35
AC048KN4DCH/AA 0.48 0.48 0.35 22.08 35
AC048JNHDCH/AA 0.48 0.48 1.9 1.9 25.53 40
AC048KNZDCH/AA 0.48 0.48 4.15 26.36 40
AC048MNHDCH/AA 0.48 0.48
2
2
26.5 40
C
AC030JXSCCH/AA
AC030JN4DCH/AA
20.00
0.48 0.48 0.35 26.31 45
AC030JNHDCH/AA 0.48 0.48 1.9 1.9 29.76 45
AC030KNZDCH/AA 0.48 0.48 2.35 32 45
AC036JXSCCH/AA
AC036JN4DCH/AA
20.00
0.48 0.48 0.35 26.31 45
AC036JNHDCH/AA 0.48 0.48 1.9 1.9 29.76 45
AC036KNZDCH/AA 0.48 0.48 4.15 32 45
AC054KXADCH/AA AC054KNZDCH/AA 28.50 0.48 0.48 5.05 41.64 70