12
1. Voltage range
- Units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range
limits
2. Maximum allowable voltage variation between phases is 2%.
3. Wire size & type must comply with the applicable local and national code.
- Wire size : Based on the value of MCA.
- Wire type : 60245 IEC57(IEC) or H05RN-F(CENELEC) grade or more.
4. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
5. MCA represents maximum input current.
MFA represents capacity which may accept MCA
Abbreviations
- MCA : Min. Circuit Amps. (A)
- MFA : Max. Fuse Amps. (A)
6. This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to Ssc(*2)
at the interface point between the users supply and the public system. It is the responsibility of the installer or user of
the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is
connected only to a supply with a short-circuit power Ssc greater than or equal to Ssc(*2).
[Ssc (*2)]
Model Ssc[MVA]
AC071HCADKH
2.209
AC060HCADKH
0.758
AC052HCAPKH
0.577
Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed exible cord.
(Code designation IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC: H07RN-F)
Power supply
Communation Cable
Power supply Max/Min(V)
Indoor Power Cable
, 220-240V, 50Hz ±10%
2.5mm², 3wires
0.75~1.5mm², 2wires
Between Indoor unit and Outdoor unit Connection Cable Specications(Common in use)
When installing the indoor unit in a computer room or net work room, use the double
shielded (Tape aluminum / polyester braid + copper ) cable of FROHH2R type.
1-phase terminal block spec
AC power : M4 screw
1(L) 2(N)
N
L
11.4 10.1
Communication : M4 screw
10.1
11.4
Connecting the cable