Installing DPM
DPM allowable Outdoor and indoor unit models
DPM allowable Outdoor and indoor unit models
Outdoor unit models
2 indoor units connection
Indoor unit
AC071HCADKH AC035HBMDKH
Installation of multiple indoor units should consist of units that have the same capacity.
Space requirements for indoor and outdoor units and piping installation
(Refer to page 8~9 installation specication.)
- Two indoor units should be installed in one area which is not divided by a wall.
- The distance between two indoor units should be within a straight-line of 10m.
- After branching, the distance between the piping connected to the two indoor units
should be within 1m.
- The height dierence between two units should be within 0.5m.
- Use the joint KIT that is only for DPM. (Please refer to the table below)
DPM KIT
2-Indoor unit connection
MXJ-2D2509K