Installation Procedure
Main power terminal block specifications
1-phase terminal block specifications
AC090/100/120/140MXADKH, AC120MXASEH
1(L) 2(N)
F1 F2
LN
15 12 11.4
10.1
3-phase terminal block specifications
AC090/100/120/140MXADNH
1(L) 2(N) L1(R) L2(S) L3(T) N
9.95 11.55 10.1
F1 F2
11.4
Main power cable specifications
The power cable is not supplied with air conditioner.
Select the power supply cable in accordance with relevant local and national regulations.
Wire size must comply with the applicable local and national code.
Specifications for local wiring power cord and branch wiring are in compliance with local cord.
Single phase
Indoor unit Outdoor unit Hz Volts Min. Max. Cooling Heating Indoor unit Total MCA MFA
AC090MN4DKH
AC090MXADKH
50 220 to 240 198 264 24.0 24.0 1.0 25.0 25.0 30.0
AC090MN4PKH
50 220 to 240 198 264 24.0 24.0 1.5 25.5 25.5 30.0
AC090MNMDKH
50 220 to 240 198 264 24.0 24.0 2.5 26.5 26.5 30.0
AC100MN4DKH
AC100MXADKH
50 220 to 240 198 264 24.0 24.0 1.0 25.0 25.0 30.0
AC100MN4PKH
50 220 to 240 198 264 24.0 24.0 1.5 25.5 25.5 30.0
AC100MNMDKH
50 220 to 240 198 264 24.0 24.0 2.5 26.5 26.5 30.0
AC100MNCDKH
50 220 to 240 198 264 24.0 24.0 2.0 26.0 26.0 30.0
AC100MNTDEH
50 220 to 240 198 264 24.0 24.0 1.1 25.1 25.1 30.0
AC120MN4DKH
AC120MXADKH
50 220 to 240 198 264 24.0 24.0 1.0 25.0 25.0 30.0
AC120MN4PKH
50 220 to 240 198 264 24.0 24.0 1.5 25.5 25.5 30.0
AC120MNMDKH
50 220 to 240 198 264 24.0 24.0 2.5 26.5 26.5 30.0
AC120MNCDKH
50 220 to 240 198 264 24.0 24.0 2.0 26.0 26.0 30.0
AC120MNMSEH
AC120MXASEH 50 220 to 240 198 264 24.0 24.0 3.5 27.5 27.5 30.0
AC140MN4DKH
AC140MXADKH
50 220 to 240 198 264 32.0 32.0 1.0 33.0 33.0 40.0
AC140MN4PKH
50 220 to 240 198 264 32.0 32.0 1.5 33.5 33.5 40.0
AC140MNMDKH
50 220 to 240 198 264 32.0 32.0 2.5 34.5 34.5 40.0
AC140MNCDKH
50 220 to 240 198 264 32.0 32.0 2.0 34.0 34.0 40.0
3-phase
Indoor unit Outdoor unit Hz Volts Min. Max. Cooling Heating Indoor unit Total MCA MFA
AC090MNMDKH
AC090MXADNH 50 380 to 415 342 456.5 16.1 16.1 2.5 18.6 18.6 18.6
AC100MN4DKH
AC100MXADNH
50 380 to 415 342 456.5 16.1 16.1 1.0 17.1 17.1 17.1
AC100MN4PKH
50 380 to 415 342 456.5 16.1 16.1 1.5 17.6 17.6 17.6
AC100MNMDKH
50 380 to 415 342 456.5 16.1 16.1 2.5 18.6 18.6 18.6
AC100MNCDKH
50 380 to 415 342 456.5 16.1 16.1 2.0 18.1 18.1 18.1
AC100MNTDEH
50 380 to 415 342 456.5 16.1 16.1 1.1 17.2 17.2 17.2
AC120MN4DKH
AC120MXADNH
50 380 to 415 342 456.5 16.1 16.1 1.0 17.1 17.1 17.1
AC120MN4PKH
50 380 to 415 342 456.5 16.1 16.1 1.5 17.6 17.6 17.6
AC120MNMDKH
50 380 to 415 342 456.5 16.1 16.1 2.5 18.6 18.6 18.6
AC120MNCDKH
50 380 to 415 342 456.5 16.1 16.1 2.0 18.1 18.1 18.1
AC140MN4DKH
AC140MXADNH
50 380 to 415 342 456.5 16.1 16.1 1.0 17.1 17.1 17.1
AC140MN4PKH
50 380 to 415 342 456.5 16.1 16.1 1.5 17.6 17.6 17.6
AC140MNMDKH
50 380 to 415 342 456.5 16.1 16.1 2.5 18.6 18.6 18.6
AC140MNCDKH
50 380 to 415 342 456.5 16.1 16.1 2.0 18.1 18.1 18.1