Installation Procedure
English
Installation Procedure
Connect the rated cables only.
Connect using a driver which is able to apply the
rated torque to the screws.
If the terminal is loose, fire may occur caused by arc.
If the terminal is connected too firmly, the terminal
may be damaged.
Tightening torque (kgf⋅cm)
M4 12.0 to 18.0
M5 20.0 to 30.0
• 1 Nm = 10 kgfcm
CAUTION
When connecting cables, you can connect the cables
to the electrical part or connect them through the
holes below depending on the spot.
Connect the communication cable between the
indoor and outdoor units through a conduit to protect
against external forces, and feed the conduit through
the wall together with refrigerant piping.
Remove all burrs at the edge of the knock-out hole
and secure the cable to the outdoor knock-out using
lining and bushing with an electrical insulation such
as rubber and so on.
Must keep the cable in a protection tube.
Keep distances of 50mm or more between power
cable and communication cable.
When the cables are connected through the hole,
remove the Plate bottom.
Outdoor-to-indoor power and communication
cables specifications
Indoor power supply
Power supply Max/Min (V) Indoor power cable
1ø, 220-240V,
50 Hz
±10% 1.5 mm²
Ĺ
, 3 wires
Communication cable
0.75 to 1.5 mm², 2 wires
Power supply cords of parts of appliances for
outdoor use shall not be lighter than polychloroprene
sheathed flexible cord. (Code designation IEC:60245
IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 /
CENELEC: H07RN-F)
When installing the indoor unit in a computer room
or net work room, use the double shielded (tape
aluminium / polyester braid + copper ) cable of
FROHH2R type.
Step 4 Optional: Extending the power
cable
1 Prepare the following tools.
Tools Spec Shape
Crimping pliers MH-14
Connection sleeve
(mm)
20xØ6.5
(HxOD)
Insulation tape
Width 19
mm
Contraction tube
(mm)
70xØ8.0
(LxOD)
2 As shown in the figure, peel off the shields from the
rubber and wire of the power cable.
Peel off 20 mm of cable shields from the pre-
installed tube.
CAUTION
For information about the power cable
specifications for indoor and outdoor units, refer
to the installation manual.
After peeling off cable wires from the pre-installed
tube, insert a contraction tube.
Power cable
(Unit: mm)
20 20 20
60
120
180
Pre-installed tube for the power cable
(Unit: mm)
20