EasyManua.ls Logo

Samsung AM***FNFDEH series - Setting an indoor unit address and installation option; The procedure of option setting

Samsung AM***FNFDEH series
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E-26
Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX
05 series installation option(Detailed)
Setting an indoor unit address and installation option(Continued)
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation PAGE MODE
Use of Auto Change
Over for HR only in
Auto mode
(When setting SEG3)
Standard heating temp. O set
(When setting SEG3)
Standard cooling
temp. O set
(When setting SEG3)
Standard for mode
change
Heating
Cooling
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
0 5
0
Follow
product
option
0 0 0 0 0 1
1
Use
Auto
Change
Over for
HR only
1 0.5 1 0.5 1 1.5
2 1 2 1 2 2
3 1.5 3 1.5 3 2.5
4 2 4 2 4 3
5 2.5 5 2.5 5 3.5
6 3 6 3 6 4
7 3.5 7 3.5 7 4.5
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Explanation PAGE
(When setting SEG3)
Standard for
mode change
Cooling
Heating
(When setting SEG3)
Time required
for mode change
Compensation option for Long
pipe or height di ference
between indoor units
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication Details Indication Details
1
0 1 0 5 min. 0 Use default value
1 1.5 1 7 min.
1
1) Height difference
(*1)
is more than 30m
or
2) Distance
(*2)
is longer
than 110m
2 2 2 9 min.
3 2.5 3 11 min.
4 3 4 13 min.
2
1) Height difference
(*1)
is 15~30m
or
2) Distance
(*2)
is 50~110m
5 3.5 5 15 min.
6 4 6 20 min.
7 4.5 7 30 min.
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
0 5
Use of Auto Change Over
for HR only in Auto mode
(When setting SEG3)
Standard heating temp.
O set
(When setting SEG3)
Standard cooling temp.
O set
(When setting SEG3)
Standard for mode change
Heating
Cooling
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
1
(When setting SEG3)
Standard for mode change
Cooling
Heating
(When setting SEG3)
Time required for mode
change
Compensation option for
Long pipe or height di erence
between indoor units
- -
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
2 - - - -
Control variables when using
hot water / external heater
SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
3 - - - - -
05 series installation option
NASA_Floor Stand_AM@@@FNFDEH@_IM_EN_03678A-05.indd 26 2016-05-09 오후 5:32:39