4-4-37 MCU branch part setup error – Connect an Indoor unit to a branch part not being used
1. How to check
Check the actual use of the branch part. If it is used, turn on the Dip switch for branch part setup. After completing resetting, press
the outdoor unit's K3 button to reset or turn off to restart.
MCU BOX #0
MCU PCB
OFF
MCU
address setup
ON
Indoor unit address
Branch part use setup
4 2 2 0 5 6
0
Branch A B C D E F
MCU BOX #1
MCU PCB
OFF
MCU
address setup
ON
Indoor unit address
Branch part use setup
4 0 1 2 5 7
1
Branch A B C D E F
MCU BOX #1
MCU PCB
OFF
ON
1 3 7 9 0 0
1
Branch A
B C D E
0
F
MCU BOX #1
MCU PCB
OFF
MCU address setup
ON
Indoor unit
Indoor unit address
Branch part use setup
4 4 2 1 5 6
0
Branch A
4
B
C D E
5
F
62
Outdoor unit display
Indoor unit display
Operation Timer
Criteria
• Occurs when MCU PIPE is set as being used, yet not connected to an indoor unit
Cause of problem
• Pipe is not installed to the indoor unit with assigned address on MCU