EasyManua.ls Logo

Samsung AM024FN4DCH/AA - Page 224

Samsung AM024FN4DCH/AA
404 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
4-24 Samsung Electronics
Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
(*3)
Explanation
Control variables when using hot water /
external heater
Remote Controller
Display
Indication and Details
Indication
Details
Set temp. for
heater On/Off
Delay time
for heater
On
0
At the same
time as thermo
on
No delay
1
At the same
time as thermo
on
10 minutes
2
At the same
time as thermo
on
20 minutes
3
2.7 °F
(1.5 °C)
No delay
4
2.7 °F
(1.5 °C)
10 minutes
5
2.7 °F
(1.5 °C)
20 minutes
6
5.4 °F
(3.0 °C)
No delay
7
5.4 °F
(3.0 °C)
10 minutes
8
5.4 °F
(3.0 °C)
20 minutes
9
8.1 °F
(4.5 °C)
No delay
A
8.1 °F
(4.5 °C)
10 minutes
B
8.1 °F
(4.5 °C)
20 minutes
C
10.8 °F
(6.0 °C)
No delay
D
10.8 °F
(6.0 °C)
10 minutes
E
10.8 °F
(6.0 °C)
20 minutes
(*1)
Height dierence : The dierence of the height between the corresponding indoor uint and the indoor unit installed at the lowest
place.
For example, When the indoor unit is installed 40m(131.23 ft) higher than the indoor unit installed at the lowest
place, select the option 1.
(*2)
Distance : The dierence between the pipe length of the indoor unit istalled at farthest place from an outdoor unit and the pipe
length of the corresponding indoor unit from an outdoor unit.
For example, when the farthest pipe length is 100m(328 ft) and the corresponding indoor unit is 40m(131.23ft) away
from an outdoor unit, select the option 2.
(100m(328 ft) - 40m(131.23 ft) = 60m(196.85ft))
(*3)
Heater operation when the SEG9 of 02 series installation option is set to using hot water heater or when SEG15 is set to using
external heater
e.g. 1) Setting 02 series SEG9 =1 / Setting 05 series SEG18 = 0: Hot water heater is turned on at the same time as the heating ther-
mostat is on, and turned o when the heating thermostat is o.
e.g. 2) Setting 02 series SEG15 =2 / Setting 05 series SEG18 =A:
Room temp. ≤ set temp. + f(heating compensation temp.)
- External heater is turned on when the temperature is maintained as 8.1 °F(4.5 °C) for 10 minutes.
Room temp. > set temp. + f(heating compensation temp.)
- External heater is turned o when the temperature is maintained as 8.1 °F(4.5 °C) + 1.8 °F(1 °C)
(1 °C is the Hysteresis for On/O selection.)

Table of Contents

Related product manuals