EasyManua.ls Logo

Samsung AM024FN4DCH/AA - Simultaneous Indoor Heat Exchangers EVA IN, out Sensor Dislocation Error (Open;Short)

Samsung AM024FN4DCH/AA
404 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
4-52 Samsung Electronics
4-4-8
Simultaneous Indoor Heat Exchanger's EVA IN, OUT sensor dislocation error (Open/Short)
1. How to diagnose
1) During Cooling Operation
Tcond, out - Tair, out > 3°C OK
Tair, in - Teva, out > 4°C NO
Tair, in - Teva, out > 4°C NO
Compressor in operation &
Indoor unit operation & Thermo On
OK
Error details
Simultaneous indoor heat exchanger's
EVA IN, OUT sensor dislocation error
2) During Heating operation
Average high pressure > 25kg/
OK
Average low pressure > 8.2kg/
OK
Teva, out - Tair, out ≥ 3°C NO
Tair, in - Teva, out ≥ 2°C NO
Tcond, out - Tair, out < -2°C OK
Compressor in operation &
Indoor unit operation & Thermo On
OK
Error details
Simultaneous Indoor heat exchanger's
EVA IN, OUT sensor dislocation error
2. How to check
Check if an Indoor heat exchanger's EVA IN, OUT sensor has been dislocated then is correct after assembling.

Table of Contents

Related product manuals