Product Specifications
Samsung Electronics 2-11
Indoor Unit(cont.)
QSlim duct(cont.)
Model AM071FNLDEH/TK AM090FNLDEH/TK AM112FNLDEH/TK AM128FNLDEH/TK AM140FNLDEH/TK
Power Supply ø/V/Hz 1/220~240/50 1/220~240/50 1/220~240/50 1/220~240/50 1/220~240/50
Mode*
1)
HP / HR HP / HR HP / HR HP / HR HP / HR
Performance
Capacity
Cooling*
2)
kW 7.1 9.0 11.2 12.8 14.0
Btu/h 24,200 30,700 38,200 43,600 47,700
Heating*
3)
kW 8.0 10.0 12.5 13.8 16.0
Btu/h 27,200 34,100 42,600 47,000 54,500
Condensate (with High fan speed) Liters/h 2.87 3.83 4.63 4.95 5.26
Power
Input W 120 170 170 200 220
Running Current A 0.6 0.96 0.96 1.28 1.43
Sound Level Sound Pressure (High/Low)*
4)
dB(A) 47 / 47 43 / 44 43 / 44 45 / 46 45 / 46
Fan
Type - Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan
Motor
Model - YSK140-60-4B DL-12840SSBC DL-12840SSBC DL-12840SSBC DL-12840SSBC
Type - Non Feedback SSR BLDC BLDC BLDC BLDC
Output W *5) *5) *5) *5) *5)
Airflow Rate
Cooling (High) m
3
/min 16.5 29.0 31.2 34.0 36.0
Heating (High) m
3
/min 20.0 34.0 34.0 36.0 38.0
External Static Pressure
Standard(Min.~Max)
mmH2O 2 (0~4) 3 (0~6) 3 (0~6) 3 (0~6) 3 (0~6)
Refrigerant
Type - R410A R410A R410A R410A R410A
Control Method - EEV EEV EEV EEV EEV
Temperature Control -
Micom&Thermistors Micom&Thermistors Micom&Thermistors Micom&Thermistors Micom&Thermistors
Safety Devices - Fuse Fuse Fuse Fuse Fuse
Piping
Connections
Liquid (Flare) ø, mm 9.52 9.52 9.52 9.52 9.52
Gas (Flare) ø, mm 15.88 15.88 15.88 15.88 15.88
Drain ø, mm VP25 (OD 32,ID 25) VP25 (OD 32,ID 25) VP25 (OD 32,ID 25) VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Weight
Net Weight kg 30.0 44.0 44.0 46.0 46.0
Shipping Weight kg 35.0 52.0 52.0 54.0 54.0
Dimensions
Net Dimensions (W x H x D) mm 1,100x199x600 1,300x295x690 1,300x295x690 1,300x295x690 1,300x295x690
Shipping Dimensions (W x H x D) mm 1350x280x710 1575x370x835 1575x370x835 1575x370x835 1575x370x835
Functions
Auto Restart - O O O O O
Auto Swing - X X X X X
Group/Individual Control - O O O O O
External Contact Control - O O O O O
Trouble Shooting by LED - X X X X X
Standard
Accessories
Installation Manual - O O O O O
Operation Manual - O O O O O
Pattern Sheet for Installation - X X X X X
Flexible Drain Hose - O O O O O
Filter / Safety Grille - Filter (Washable) Filter (Washable) Filter (Washable) Filter (Washable) Filter (Washable)
Drain Pump (Pumping speed, lift) - MR-BH01 MR-BH01 MR-BH01 MR-BH01 MR-BH01
Optional
Accessories
Wireless Remote Controller - MR-DH00 MR-DH00 MR-DH00 MR-DH00 MR-DH00
Duct Receiver Kits
Receiver
- MRK-A10 MRK-A10 MRK-A10 MRK-A10 MRK-A10
Receiver Wire
- MRW-10A MRW-10A MRW-10A MRW-10A MRW-10A
Wired Remote
Controller
Simplified - MWR-WE10N MWR-WE10N MWR-WE10N MWR-WE10N MWR-WE10N
External Contact Interface Module MIM-B14 MIM-B14 MIM-B14 MIM-B14 MIM-B14
Drain Pump
MDP-E075SEE3D MDP-E075SEE3D MDP-E075SEE3D
MDP-E075SEE3D MDP-E075SEE3D
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Nominal cooling capacities are based on;
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, 24˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*3) Nominal heating capacities are based on;
- Indoor temperature : 20˚C DB, 15˚C WB
- Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications may be subject to change without prior notice for product improvement.