EasyManua.ls Logo

Samsung AM028FNLDEH/TK - Page 198

Samsung AM028FNLDEH/TK
334 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
Samsung Electronics 4-53
4-4-8
Simultaneous Indoor Heat Exchanger's EVA IN, OUT sensor dislocation error (Open/Short)
1. How to diagnose
1) During Cooling Operation
Tcond, out - Tair, out > 3°C OK
Tair , in - Teva, out > 4°C NO
Tair , in - Teva, out > 4°C NO
Compr essor in operation &
Indoor unit operation & Thermo On
OK
Error details
Simultaneous indoor heat exchanger's
EVA IN, OUT sensor dislocation error
2) Du
ring Heating operation
Average high pressure > 25kg/
OK
Average low pressure > 8.2kg/
OK
Teva, out - Tair, out3°C NO
Tair , in - Teva, out2°C NO
Tcond, out - Tair, out < -2°C OK
Compr essor in operation &
Indoor unit operation & Thermo On
OK
Error details
Simultaneous Indoor heat exchanger's
EVA IN, OUT sensor dislocation error
2. How to check
Check if an Indoor heat exchanger's EVA IN, OUT sensor has been dislocated then is correct after assembling.

Table of Contents

Other manuals for Samsung AM028FNLDEH/TK

Related product manuals