17
4. Capacity Table
Model
Outdoor
temperature
(°C, DB)
Indoor temperature (°C, DB)
16.0 18.0 20.0 22.0 24.0
TC TC TC TC TC
DB WB kW kW kW kW kW
3.60
-20 -21 2.40 2.40 2.30 2.30 2.30
-17 -18 2.60 2.50 2.40 2.40 2.30
-15 -16 2.70 2.60 2.50 2.50 2.40
-12 -13 2.80 2.70 2.70 2.60 2.60
-10 -11 2.90 2.90 2.90 2.80 2.80
-7 -8 3.10 3.10 3.00 3.00 2.90
-5 -6 3.30 3.20 3.20 3.10 3.00
-3 -4 3.40 3.40 3.30 3.20 3.10
0 -1 3.60 3.60 3.50 3.40 3.20
3 2 3.80 3.70 3.70 3.50 3.40
5 4 3.90 3.90 3.80 3.60 3.40
7 6 4.10 4.10 4.00 3.70 3.40
9 8 4.20 4.10 4.00 3.70 3.40
11 10 4.40 4.20 4.00 3.70 3.40
13 12 4.50 4.20 4.00 3.70 3.40
15 14 4.60 4.30 4.00 3.70 3.40
5.60
-20 -21 3.90 3.80 3.80 3.70 3.70
-17 -18 4.00 4.00 3.90 3.80 3.80
-15 -16 4.20 4.10 4.00 3.90 3.80
-12 -13 4.40 4.30 4.20 4.20 4.10
-10 -11 4.60 4.60 4.50 4.40 4.40
-7 -8 4.90 4.80 4.80 4.70 4.50
-5 -6 5.20 5.10 5.00 4.90 4.70
-3 -4 5.40 5.30 5.30 5.10 4.90
0 -1 5.70 5.60 5.50 5.30 5.00
3 2 5.90 5.90 5.80 5.60 5.30
5 4 6.20 6.10 6.00 5.70 5.30
7 6 6.50 6.40 6.30 5.80 5.30
9 8 6.70 6.50 6.30 5.80 5.30
11 10 6.90 6.60 6.30 5.80 5.30
13 12 7.1 0 6.70 6.30 5.80 5.30
15 14 7.3 0 6.80 6.30 5.80 5.30
7.10
-20 -21 4.90 4.90 4.80 4.70 4.70
-17 -18 5.10 5.00 4.90 4.80 4.80
-15 -16 5.30 5.20 5.10 4.90 4.80
-12 -13 5.60 5.50 5.40 5.30 5.20
-10 -11 5.90 5.80 5.70 5.60 5.60
-7 -8 6.20 6.10 6.00 5.90 5.80
-5 -6 6.50 6.50 6.40 6.20 6.00
-3 -4 6.90 6.80 6.70 6.40 6.20
0 -1 7. 20 7.10 7.0 0 6.70 6.40
3 2 7. 60 7.5 0 7.3 0 7.1 0 6.80
5 4 7.90 7.80 7.70 7. 2 0 6.80
7 6 8.20 8.10 8.00 7.4 0 6.80
9 8 8.50 8.20 8.00 7. 40 6.80
11 10 8.70 8.40 8.00 7. 40 6.80
13 12 9.00 8.50 8.00 7. 40 6.80
15 14 9.20 8.60 8.00 7. 40 6.80
NOTE
• The performance table shows the average value of each conditions.
Wind-Free 1Way Cassette