11. Installation
38
CAUTION
Must fit tightly against body without any gap.
Install the insulation not to get wider and use the adhesives on the connection part of it to prevent moisture
from entering.
Wind the refrigerant pipe with insulation tape if it is exposed to outside sunlight.
Install the refrigerant pipe respecting that the insulation does not get thinner on the bent part or hanger of pipe.
Add the additional insulation if the insulation plate gets thinner.
Refrigerant pipe insulation
Hanger
Additional
insulation
a
a x 3
Must fit tightly against body without any gap.
All refrigerant connection must be accessible, in order to permit either unit maintenance or removal.
5 Select the insulation of the refrigerant pipe.
Insulate the gas side and liquid side pipe, noting the insulation thickness that must differ according to the pipe
size.
Standard: Less than an indoor temperature of 30°C, with humidity at 85%. If installing in a high humidity
environment, use one grade thicker insulator by referring to the table below. If installing in an unfavourable
environment, use thicker one.
The heat-resistance temperature of the insulator must be more than 120°C.
Pipe Pipe size
Insulation Type (Heating/Cooling)
Remarks
Standard
[30°C, 85%]
High humidity
[30°C, over 85%]
EPDM, NBR
Liquid
pipe
Ø6.35 to Ø9.52 9t
Internal
temperature is
higher than 120°C
Ø12.7 to Ø50.80 13t
Gas pipe
Ø6.35 13t 19t
Ø9.52 to Ø25.40
19t
25t
Ø28.58 to Ø44.45 32t
Ø50.80 25t 38t