Troubleshooting
Samsung Electronics
27
Heating Pump Out
Operation for the repair of the Individual outdoor unit, the outdoor unit refrigerant emissions to the indoor part.
Liquid pipe service valve and the gas pipe service valve operation, the operator manually need to close.
Observe low pressure using View Mode of K4 button if compressor operate.
If low pressure goes down below about 0.2 MPa.g : Immediately lock the gas side service valve, Pump Out operation is shut down.
(Pump out operation shut down : K1 button once more press or K3 button one time press)
If operation of low pressure goes down below 0.1 MPa.g : Will be stopped automatically for the protection of the compressor.
How to Initiate K1 Tact Switch 3 times~6 times
Compressor 60Hz
Indoor Unit Whole Operation (The set temperature=40°C)
4Way Valve ON (Heating Mode)
Outdoor Fan Maximum air flow
Main EEV Operation side : 700 Step (Stop side : 0 step)
Maximum Operation Time 10 minutes
Protection Control Conduct the discharge temperature, high pressure control. (Low pressure protection control is not carried out)
Low pressure is outside normal limits : Operation is shut down after gas pipe manually closed.
Etc. Entry after safety start. (Only the corresponding Outdoor Unit operation.)
To pump out more than 2 : Except communication between Outdoor Unit of relevant set after working for one,
remainder set makes Pump Out add.
Cooling Pump Down
Recover the refrigerant of Indoor Unit and Piping to outdoor side.
Liquid pipe service valve and the gas pipe service valve operation, the operator manually need to close.
If the installation of the long pipe : Any refrigerant into the outdoor unit can not be recovered, therefore should use a separate container.
Observe low pressure using View Mode of K4 button if compressor operate.
If low pressure goes down below about 0.2 MPa.g : Immediately lock the gas side service valve, Pump Out operation is shut down.
(Pump out operation shut down : K1 button once more press or K3 button one time press)
If operation of low pressure goes down below 0.1 MPa.g : Will be stopped automatically for the protection of the compressor.
How to Initiate K2 Tact Switch 3 times
Compressor Address No.1 Outdoor Unit - 60Hz (Other Outdoor Unit COMP OFF)
Indoor Unit Whole Operation (The set temperature=3°C)
4Way Valve OFF (Cooling Mode)
Outdoor Fan Maximum air flow
Main EEV Operation side : 2000 Step , Stop side : 2000 step
Maximum Operation Time 30 minutes
Etc. Does not conduct the operation of the special operation, and protection control.
Pressure and temperature is outside normal limits : Operation is shut down after gas pipe manually
closed.