33
English
Installation Procedure
Setting the indoor unit addresses (MAIN/RMC/
MCU)
1 Make sure that the power is supplied to the indoor
unit.
• If the indoor unit is not plugged in, it must include a
power supply.
2 Make sure that the panel or display is connected to the
indoor unit so that it can receive options.
Indoor unit
3 Set an address (MAIN/RMC/MCU port) for each indoor
unit using the remote control, according to your air
conditioning system plan.
• The indoor unit addresses (MAIN/RMC/MCU port)
are set to 0A0000-100000-200000-300000 by
default.
NOTE
• Also set the MCU and Indoor units address by using
Add-on
→
Change address on S-NET Pro 2.
(For more information, see the S-NET Pro 2 Help.)
• From SEG13 to SEG18 is for setting MCU address.
– MCUmodelsthatcansetaddress:MCU-S∗NEK2N,
MCU-S4NEK3N, MCU-S1NEK1N
Option No. for an indoor unit address: 0AXXXX-1XXXXX-2XXXXX-3XXXXX
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Function Page Mode
Setting main
address
100-digit of
an indoor unit
address
10-digit of an
indoor unit
address
The single digit
of an indoor unit
Indication
and details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
0 A
0
No main
address
0 to 9 10-digit 0 to 9
A
single
digit
0 to 3
A single
digit
1
Main
address
setting
mode
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Function Page -
Setting RMC
address
-
Group channel
(x16)
Group address
Indication
and details
Indication
Details
-
Indication
Details
-
Indication
Details
Indication
Details
1
0
No RMC
address
RMC1 0 to F RMC2 0 to F
1
RMC
address
setting
mode