37
English
Installation Procedure
Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
Explanation PAGE Use of external control
Setting the output of external
control / External heater signal /
Cooling operation signal /
Free Cooling control signal
S-Plasma ion Buzzer control Hours of filter usage
Indication
and Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
2
0 Disuse 0
External control
(Thermo On)
0 Disuse 0
Use
buzzer
2 1000 Hour1
ON/OFF
control
1
External control
(Operation On)
2
External heater
signal (*4)
2
OFF
control
3
External heater
signal (*4)
4
Cooling operation
signal (*5)
1 Use 1
Disuse
buzzer
6 2000 Hour
3
Window
ON/OFF
control
5
Free Cooling control
(Cooling Thermo On) (*6)
6
Free Cooling control
(Cooling/Dry Thermo
On) (*6)
Option SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
Explanation PAGE
Individual control of a
remote controller
Heating setting compensation / Removing condensate water
in heating mode
Adjusted EEV step of
stopped unit during
oil return /defrost
mode.
Motion detect sensor -
Indication and
Details
Indication
Details
Indication Details Indication
Details
Indication Details Indication Details
-
Heating Setting
Compensation
Removing Condensate
Water in Heating Mode
3
0 or 1 channel 1
0 Default Disuse
0 Default
0 Disuse
1 2 °C Disuse 1
Turn out in 30min.
without motion
2 channel 2
2 5 °C Disuse 2
Turn out in 60min.
without motion
3 Default Use (*7)
3
Turn out in 120min.
without motion
3 channel 3
4
Turn out in 180min.
without motion
4 2 °C Use (*7)
1
Adjusted
EEV
positon
5
Turn out in 30min.
without motion or
*advanced function
4 channel 4
6
Turn out in 60min.
without motion &
*advanced function
5 5 °C Use (*7)
7
Turn out in 120min.
without motion &
*advanced function
8
Turn out in 180min.
without motion &
*advanced function
* Advanced function: Controlling cooling/heating current or power saving with motion detect.
(*1) When Cooling or dry mode is off. The indoor fan operate in setting minutes.
(*2) Minimizing fan operation when thermostat is off
- Fan operates for 20 seconds at an interval of 5 minutes in heat mode.
- Fan stops or operates Ultra low in Cooling when thermostat is off.