40
Installation Procedure
English
Installation Procedure
Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
Explanation - - - - - Control variables when using hot water / external heater (*4)
Indication
and Details
Indication Details - - - - Indication
Details
Set temp. for heater On/Off
Delay time for heater On
2 - - - -
0 At the same time as thermo on No delay
1 At the same time as thermo on 10 minutes
2 At the same time as thermo on 20 minutes
3 1.5 °C No delay
4 1.5 °C 10 minutes
5 1.5 °C 20 minutes
6 3.0 °C No delay
7 3.0 °C 10 minutes
8 3.0 °C 20 minutes
9 4.5 °C No delay
A 4.5 °C 10 minutes
B 4.5 °C 20 minutes
C 6.0 °C No delay
D 6.0 °C 10 minutes
E 6.0 °C 20 minutes
Option SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
Explanation PAGE - - - Forcing FAN Operation for Heating and Cooling -
Indication
and Details
Indication Details - - - Indication
Details
-
Cooling Fan
Setting
Heating Fan
Setting
3 - - -
0 Disuse Disuse
-
1 Disuse
Use (Fan: User
setting)
2 Disuse Use (Fan: High)
3 Disuse Use (Fan: Low)
4
Use (Fan: User
setting)
Disuse
5
Use (Fan: User
setting)
Use (Fan: User
setting)
6
Use (Fan: User
setting)
Use (Fan: High)
7
Use (Fan: User
setting)
Use (Fan: Low)
8 Use (Fan: High) Disuse
9 Use (Fan: High)
Use (Fan: User
setting)
A Use (Fan: High) Use (Fan: High)
B Use (Fan: High) Use (Fan: Low)
C Use (Fan: Low) Disuse
D Use (Fan: Low)
Use (Fan: User
setting)
E Use (Fan: Low) Use (Fan: High)
F Use (Fan: Low) Use (Fan: Low)