Compressor starting/rotation error (Error Code : E461, E467) (cont.)
1. Change the compressor wire Turn on the
power End service
2. Change the compressor wire Turn on the
power End service
3. Change the compressor wire Turn on the
power End service
No
Is the
compressor wire
assembled in following color?
U: RED, V: BLU, W: YEL Check for wire
disconnection on PBA and COMP.
2. Is the terminal within the compressor
wire housing firmly assembled?
3. Is there any problem, such as
disconnected housing or cut,
on some of the
compressor wire?
Yes
Yes
Cont.
Change the outdoor unit PBA and check
for normal operation End service
W
V
U
* Do not change the EMI/outdoor unit main/ Indoor unit main PBA when E461, E467 error occurs.
It is Compressor, inverter PBA related error, therefore it is not related to above PBA.
* Make sure to check if service valve is open.
If the service valve is close, damage could occur due to pressure difference during operation.