11
ENGLISH
Base ground work
< When installing on the ground >
Drain hole
150mm (6inch) or more
< When installing on the roof >
Install the outdoor unit
horizontally on the ground
150mm (6inch) or more
X The outdoor unit should be supported within the range of measurement below for base ground work.
Unit: mm (inch)
Anchor bolt position
330 (12.99)
620 (24.40)
940 (37.00)
360 (14.17)
384 (15.11)
X When the outdoor unit needs to be supported, fix it with wire as shown in the
picture.
- Slightly unwind the four screws on the cover top of the outdoor unit.
- Wind wires round the four screws and fasten the screws again.
- Fix the wires to the ground.
• If the outdoor unit is not fixed securely, product may fall and it might cause loss of life or property damage.
• Do not install the outdoor unit on a wood palette.
• Fix the outdoor unit securely to the base ground with anchor bolts.
• The manufacturer is not responsible for the damage occurred by not adhering to the standard of the installation.
• To protect the outdoor unit from external condition such as rain, install it on the base ground and connect the
drain pipe to the drainage.
CAUTION