92 Samsung Electronics
Check Operation & Amount of Refriherant Automatically Checking
3) Pressure sensor
Ŷ Inspection item : High/Low Pressure sensor of the independent installed Outdoor Unit.
ŶError code: None (The resulting report "Undetermined")
Ŷ Determine the status of the Pressure sensor of the independent installed Outdoor Unit before the compressor start.
Ŷ If the judgment of Outdoor Unit Pressure sensor is "Undetermined" : Checking in accordance with the following order.
[Caution]
- If the Outdoor Unit with a history of operation (Automatic commissioning inclusion) : Maintain the vacuum mode for more than 5 minutes.
Yes
No
Is Pressure sensor connector properly connect?
Yes
Replace Hub PCB
No
Is voltage 5V between
3, 4 pin of PCB Pressure sensor terminal?
Yes
Replace PCB
No
Is deviation of outdoor
unit as following?"High pressure Max
/Min deviation : less than 2"
Check the pressure sensor breakdown
Complete
Vacuum mode of Outdoor Unit
Check the Pressure sensor breakdown after the saturation pressure
of the outdoor temperature or connect the manifold gauge to check the pressure.