Product Specications
Samsung Electronics 2-57
Product Specications
2-56 Samsung Electronics
Outdoor Unit (cont.)
Type
DVM S
Model AM080MXVAFCAAZ AM100MXVAFCAAZ AM120MXVAFCAAZ AM140MXVAFCAAZ AM160MXVAFCAAZ AM180MXVAFCAAZ AM200MXVAFCAAZ
Mode - Cooling Only Cooling Only Cooling Only Cooling Only Cooling Only Cooling Only Cooling Only
Power Supply Φ, #, V, Hz 3,3,208-230,60 3,3,208-230,60 3,3,208-230,60 3,3,208-230,60 3,3,208-230,60 3,3,208-230,60 3,3,208-230,60
Performance
HP HP 8.00 10.00 12.00 14.00 16.00 18.00 20.00
Capacity
(Nominal)
Cooling
kW 22.40 28.00 33.60 40.00 45.00 50.40 56.00
Btu/h 76,400 95,500 114,600 136,500 153,500 172,000 191,100
Heating
kW - - - - - - -
Btu/h - - - - - - -
Power
Power Input
(Nominal)
Cooling 1)
kW
4.35 5.50 7.22 8.47 10.64 10.66 11.45
Heating 2)
Current Input
(Nominal)
Cooling 1)
A
12.70 16.00 21.10 24.70 31.00 31.10 33.40
Heating 2)
Max Current 26.0 32.2 35.0 45.4 51.2 56.2 65.0
MCA 26.00 (MCA) 32.20 (MCA) 35.00 (MCA) 45.4 (MCA) 51.2(MCA) 56.20 (MCA) 65.00 (MCA)
MFA A 40.00 50.00 50.00 63.00 63.00 63.00 75.00
COP
Nominal Cooling 1) - 5.15 5.09 4.65 4.72 4.23 4.73
4.89
Nominal Heating 2) - - - - - - - -
Compressor
Type - SSC Scroll x 1 SSC Scroll x 1 SSC Scroll x 1 SSC Scroll x 2 SSC Scroll x 2 SSC Scroll x 2 SSC Scroll x 2
Output kW × n (5.09) (6.45) (6.45) (5.09x2) (5.09x2) (6.45x2) (6.45x2)
Model Name - DS-GB052FBVASG x 1 DS4GJ066EVASG x 1 DS4GJ066EVASG x 1 DS-GB052FBVASG x 2 DS-GB052FBVASG x 2 DS4GJ066EVASG x 2 DS4GJ066EVASG x 2
Oil
Type - PVE PVE PVE PVE PVE PVE PVE
Initial Charge cc 1100 1100 1100 2200 2200 2200 2200
Fan
Type - Propeller Propeller Propeller Propeller Propeller Propeller Propeller
Output x n W 830.0 x 1 830.0 x 1 830.0 x 1 620.0 x 2 620.0 x 2 620.0 x 2 620.0 x 2
Air Flow Rate CMM 170 170 220 255 255 260 265
l/s 2,833 2,833 3,667 4,250 4,250 4,333 4,417
External Static Pressure Max. mmAq 8.00 8.00 8.00 8.00 8.00 8.00 8.00
Pa 78.45 78.45 78.45 78.45 78.45 78.45 78.45
Piping
Connections
Liquid Pipe Φ, mm 9.52 9.52 12.70 12.70 12.70 15.88 15.88
Φ, inch 3/8" 3/8" 1/2" 1/2" 1/2" 5/8" 5/8"
Gas Pipe Φ, mm 19.05
22.22 28.58 28.58 28.58 28.58 28.58
Φ, inch 3/4" 7/8" 1 1/8" 1 1/8" 1 1/8" 1 1/8" 1 1/8"
Discharge Gas Pipe Φ, mm - - - - - - -
Φ, inch - - - - - - -
Oil Equalizing Pipe Φ, mm - - - - - - -
Φ, inch - - - - - - -
Installation
Limitation
Max. Length m 200 200 200 200 200 200 200
Max. Height m 110.0 110.0 110.0 110.0 110.0 110.0 110.0
Field
Wiring
Power Source Wire mm2 - - - - - - -
Transmission Cable mm2 - - - - - - -
Refrigerant
Type - R410A R410A R410A R410A R410A R410A R410A
Factory Charging kg 5.5 5.5 6.5 7.7 7.7 8.4 8.4
Sound 5)
Sound Pressure(Dev.) dB(A) 68 68 71 72 73 73 73
Sound Pressure(TDB) 57 58 62 61.0 63.0 64.0 65.0
Sound Power(TDB) 77 79 81 81.0 83.0 86.0
87.0
External
Dimension
Net Weight kg 178 185.5 196.5 282 282 305 305
Shipping Weight kg 190 197.5 208.5 301 301 324 324
Net Dimensions (WxHxD) mm 880 x 1,695 x 765 880 x 1,695 x 765 880 x 1,695 x 765 1,295 x 1,695 x 765 1,295 x 1,695 x 765 1,295 x 1,695 x 765 1,295 x 1,695 x 765
Shipping Dimensions (WxHxD) mm 948 x 1,887 x 832 948 x 1,887 x 832 948 x 1,887 x 832 1,363 x 1,887 x 832 1,363 x 1,887 x 832 1,363 x 1,887 x 832 1,363 x 1,887 x 832
Operating
Temp. Range
Cooling
℃
-5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0
Heating
℃
- - - - - - -
1. Proper form capacity standard of air conditioning
- Cooling capacity : It is figures that appear in indoor 27˚C DB/19°C WB, outdoor 35˚C DB, length 7.5m of piping, fall 0m standard.
- Heating capacity : It is figures that appear in indoor 20˚C DB, outdoor 7˚C DB, length 7.5m of piping, fall 0m standard.
2. If proper form heating capacity is outdoor temperature 7˚C standard and outdoor temperature goes down by below zero, heating capacity can drop according to temperature condition.
3. Need special load calculation in case of use by main heating in the winter, and please buy product for low temperature that heating effect excels at low temperature.
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m).
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m.