Aɇϑϑѣʀɇϩͱ Example Remarks
Maximum
allowable
length after
branch joint
First branch
ͱϩɇθϩ˵ʪϑϩ
Indoor unit
Pipe length
45 m or less
Installing only with Y-joint
ɵʀʒʪ˙˝Χߦߧ
-
Installing with Y-joint and
distribution header
ߦߧ
Installing only with
distribu-tion header
ߦߧ
ߦߧ߫ߢ
Note 1)
ŵʪαЇθʪʒʀͱʒϩͱϑЇϑϩɵʪϑɇϩϑѣʪʒ
-
EEV kit Model name Remarks
kkǤϩ
Indoor unit
Actual pipe
length
2 m
MEV-E24SA
1 indoor
Apply to products without EEV
(Wall mount & ceiling)
MEV-E32SA
20 m or less
MXD-E24K132A
2 indoorMXD-E24K200A
MXD-E32K200A
MXD-E24K232A
3 indoor
MXD-E24K300A
MXD-E32K224A
MXD-E32K300A
࢜
Please refer to the EEV Kit manual.
Note 1) Required condition
Aɇϑϑѣʀɇϩͱ Condition Example
θϑϩɵθɇʀ˵ͱϩ
Farthest Indoor unit
ߦߧɵʀʒʪ˙˝Χ߫ߢࡤɵθɇʀ˵ΧΧʪϑ
(b, c, d, e, f, g) size must be increased by 1
grade
Total length of
extended pipe
If the size of pipe (main pipe), between the
ѣθϑϩɵθɇʀ˵ͱϩɇʒϩ˵ʪͱЇϩʒͱͱθЇϩࡥϑͱϩ
increased by 1 grade, a+(b+c+d+e+f+g)×2
˵Χߣߢߢߢ
If the size of pipe (main pipe), between the
ѣθϑϩɵθɇʀ˵ͱϩɇʒϩ˵ʪͱЇϩʒͱͱθЇϩࡥϑ
increased by 1 grade, (a+b+c+d+e+f+g)×2
˵Χߣߢߢߢ
kɇʀ˵ǽࣛͱϩ
Each indoor unit
˵ࡥࡥࡥࡰΧߦߧ
Difference between the distance of the outdoor unit to the farthest indoor
ЇϩɇʒʪɇθʪϑϩʒͱͱθЇϩߦߧࡥ࣑ɇɵʀʒʪ˙˝Χ࣒࣑ࣛɇ˵࣒ߦߧ
Note 2) When indoor unit is located at higher level than outdoor unit, allowable height difference is 110m, (If
the height difference is over 40m, contact your local dealer for more information.)
but when the indoor unit is located at lower level than outdoor unit, allowable height difference is
110m (If the height difference is over 50m, need to decide whether to install PDM kit or not.)
Model name of the PDM kit : MXD-A38K2A, MXD-A12K2A, MXD-A58K2A
Refrigerant pipe installation