Operating Instructions and Installation
3-7
3-2-2(b) Refrigerant Adjustment
3-2-2(c) Flare unt fixing torque
Class For installation For service
Outter diameter
ø 6.35 (9000Btu, 12000Btu)
(Liquid Side)
ø 9.52 (9000Btu)
(Gas Side)
ø 12.7 (12000Btu)
(Gas Side)
160
300
500
200
350
550
Fixing Torque Final Torque
Torque (kg-cm)
Connection
Pipe Length
5m
(standard)
6~15m
Air-Purge
Method
Refer to the
detailed Air-Purge
Procedure
Refrigerant
Adjustment
Unnecessary
Add 20g of refrigerant
(R-22) for every 1m.
Air-Purge
Method
Purge air using a
vaccum pump
or an additional
refrigerant cylinder.
Refrigerant
Quantity
refer to
specification sheet
Add 20g of refrigerant
(R-22) for every 1m.
20 25 30 35 40 45
32.4
30.6
28.8
27.0
24.0
21.5
6.5
6
5.5
5
4.5
4
3.5
Outdoor inlet air DB temp.(˚C)
• MODEL NAME : AQV12A1ME (UQV12A1ME)
AQV12A2ME (UQV12A2ME)
S H 1 2 VA 1 ( S H 1 2 VA 1 X )
S H 1 2 VA 2 ( S H 1 2 VA 2 X )
20 25 30 35 40 45
32.4
30.6
28.8
27.0
24.0
21.5
7
6.5
6
5.5
5
4.5
4
Outdoor inlet air DB temp.(˚C)
• MODEL NAME : AQV09A1ME (UQV09A1ME)
AQV09A2ME (UQV09A2ME)
S H 0 9 VA 1 ( S H 0 9 VA 1 X )
S H 0 9 VA 2 ( S H 0 9 VA 2 X )
Samsung Electronics