12. Capacity Table
Combination
(Capacity Index)
Combination
(Total)
Combination
(%)
Outdoor
Temperature
(℃,DB)
Indoor Temperature(℃, DB)
14 16 18 20 21 22 24
TC(kW) PI(kW) TC(kW) PI(kW) TC(kW) PI(kW) TC(kW) PI(kW) TC(kW) PI(kW) TC(kW) PI(kW) TC(kW) PI(kW)
2500 2500 3500 3500 12000 150%
-15 5.32 1.69 5.16 1.72 5.01 1.74 4.88 1.76 4.82 1.77 4.77 1.78 4.68 1.79
-10 6.38 1.78 6.20 1.81 6.04 1.83 5.90 1.85 5.84 1.86 5.78 1.87 5.68 1.89
-5 7.43 1.87 7.25 1.90 7.08 1.92 6.93 1.95 6.86 1.96 6.80 1.97 6.69 1.98
0 8.49 1.96 8.29 1.99 8.12 2.01 7.96 2.04 7.88 2.05 7.82 2.06 7.70 2.08
2 8.91 1.99 8.71 2.02 8.53 2.05 8.37 2.07 8.29 2.08 8.22 2.09 8.10 2.11
7 9.97 2.08 9.76 2.11 9.57 2.14 9.30 2.13 9.32 2.18 9.24 2.19 9.11 2.21
10 10.61 2.13 10.39 2.16 10.20 2.19 10.02 2.22 9.94 2.23 9.86 2.24 9.72 2.26
15 11.67 2.22 11.44 2.25 11.24 2.28 11.05 2.31 10.96 2.32 10.88 2.33 10.73 2.35
NOTE
Cooling capacity is based on 27°CDB / 19°CWB (indoor temperature), 35°CDB (outdoor temperature).
Heating capacity is based on 20°CDB (indoor temperature), 7°CDB/6°CWB (outdoor temperature).
The above is the value for connecting with the following indoor units.
- 2000, 2500, 3500, 5000, 6800W class : AR07TXFCAWKNEU, AR09TXFCAWKNEU, AR12TXFCAWKNEU,
AR18TXEAAWKNEU, AR24TXEAAWKNEU
Capacities are based on the following conditions:
- Corresponding refrigerant piping length : 5m / - Level difference : 0m
The total ability of connected a indoor unit is up to 12kW
It is impossible to connect the indoor unit for one room only.
This data is reference data for temperature capacity trend.