3. Electric Characteristics3. Electric Characteristics
Capacity
(Cooling)
kW
Model
Power Supply Voltage Range
Nominal Running
Current [A]
Current [A]
ODU
Fan
Motor
Hz Voltage
Min.
(-15%)
Max.
(+15%)
Cooling Heating MCA MFA kW
4.0 AJ040TXJ2KG/EU 50 220~240 198 264 4.1 4.1 9.8 11.25 0.04
5.0 AJ050TXJ2KG/EU 50 220~240 198 264 5.6 5.9 11.8 13.75 0.04
5.2 AJ052TXJ3KG/EU 50 220~240 198 264 5.5 6.1 11.9 13.75 0.125
6.8 AJ068TXJ3KG/EU 50 220~240 198 264 8.1 8.2 1 7. 5 20.75 0.125
8.0 AJ080TXJ4KG/EU 50 220~240 198 264 8.9 9.5 17.8 20.75 0.125
10.0 AJ100TXJ5KG/EU 50 220~240 198 264 12.2 12.8 24.5 28.75 0.125
NOTE
MCA : Minimum circuit amperes
MFA : Maximum fuse amperes
Select wire size based on the value of MCA