Design Model Name Model
AJ020BXJ2CH AJ024BXJ3CH AJ036BXJ4CH AJ048BXJ5CH AJ020CXS3CH AJ024CXS4CH AJ030CXS4CH AJ036CXS4CH
Model
Capacity
[kBtu/h]
20 24 36 48 20 24 30 36
AJ009/012BNHDCH 9/12
● ● ● ● ● ● ●
AJ015BNHDCH 15
● ● ● ● ● ● ●
AJ018BNHDCH 18
● ● ● ● ● ●
AC009/012BNJDCH 9/12
● ● ● ● ● ● ● ●
AC015BNJDCH 15
● ● ● ● ● ● ● ●
AC018BNJDCH 18
● ● ● ● ● ●
AC012BNZDCH 12
● ● ● ● ● ● ● ●
AC018BNZDCH 18
● ● ● ● ● ●
AC024BNZDCH 24
● ● ● ●
■ Combination guide when applying AJ0**BNHDCH/AA (Duct S) or AC0**BNZDCH/AA (MPAH) indoor units.
- Only one AC***BNZDCH/AA (MPAH) indoor unit can be included in the combination.
- Only one AJ***BNHDCH/AA (Duct S) indoor unit can be included in the combination.
- AJ***BNHDCH/AA (Duct S) indoor units cannot be connected to outdoor unit model AJ020BXJ2CH/AA.
- If AJ0**BNHDCH/AA (Duct S) or AC0**BNZDCH/AA (MPAH) indoor units are included in the combination, the total sum of
indoor unit nominal capacity cannot exceed the outdoor unit nominal capacity (max. 100% design diversity/capacity ratio).
- If the indoor unit combination includes AJ0**BNHDCH/AA (Duct S) or AC0**BNZDCH/AA (MPAH) indoor units and does not
meet the installation combination restrictions, error code E563 error will display and the system will not operate.
- If error code E563 occurs, Cool Mode and Pipe Check operations are still possible.
Combination Guide for Systems That Include AJ***BNHDCH/AA or AC***BNZDCH/AA
Outdoor Unit Model(US code)
Mixed
Installation
4 Indoor Unit
Connection
3 Indoor Unit
Connection
2 Indoor Unit
Connection
Combination
Ratio
Outdoor
Index
JXH24J3B (AJ024BXJ3CH/AA) Not Allowed Not Allowed Not Allowed Allowed ≤ 1.0 24
JXH36J4B (AJ036BXJ4CH/AA) Not Allowed Not Allowed Allowed Allowed ≤ 1.0 36
JXH48J5B (AJ048BXJ5CH/AA) Not Allowed Allowed Allowed Allowed ≤ 1.0 48
JXH20S3C (AJ020CXS3CH/AA) Not Allowed Not Allowed Not Allowed Allowed ≤ 1.0 21
JXH24S4C (AJ024CXS4CH/AA) Not Allowed Not Allowed Allowed Allowed ≤ 1.0 24
JXH30S4C (AJ030CXS4CH/AA) Not Allowed Not Allowed Allowed Allowed ≤ 1.0 30
JXH36S4C (AJ036CXS4CH/AA) Not Allowed Not Allowed Allowed Allowed ≤ 1.0 36
*Mixed installation means mixing AJ***BNHDCH/AA and AC***BNZDCH/AA units on the same system.
CAUTION