4-34 4-35
Troubleshooting
■ If Error code is displayed on indoor or outdoor LED, check as follows;
Contents
Q1 Turn on the system. But outdoor units PCB displayed E201 or E101 Error code. Check point Remarks
Check point Remarks
Step 1
Check to power cable to indoor units.
Check to communication cable indoor units.

Contents
Q2 Turn on the system. But outdoor units PCB displayed E203 Error code.
Check point Remarks
Guidance
Outdoor communication error between
the outdoor main PCB and sub PCB.

Step 1 Check to sub PCB wire and replace it. 
Contents
Q3 Turn on the indoor units. But indoor unit displayed E121/122/123/154 Error code.
Error code
Explanation
E121 Indoor unit room temperature sensor error (open/short)
E122 Indoor unit heat exchanger in temperature sensor error (open/short)
E123 Indoor unit heat exchanger out temperature sensor error (open/short)
E154 Indoor unite fan error
Guidance
Please, all units turn off and check to indoor unit’s PCB and wire connection.
E121/122/123 error detected, replace related sensor.
Contents
Q4 Turn on the system. But indoor unit displayed E162/163 Error code.
Error code
Explanation
E162 Indoor unit EEPROM Error.
E163 Indoor unit EEPROM Option Error.
Guidance
Please, all units turn off and follow guidance.
E163 : Please reset indoor Option code.
E163 : If you don’t know about that, replace indoor unit PCB which is related.
E162 : Please replace indoor unit PCB which is related.
Contents
Q5 Turn on the system. But outdoor unit displayed E221/237/251/320 Error code.
Error code
Explanation
E221 Outside temperature sensor error (open/short)
E237 Condenser temperature sensor error (open/short)
E251 Compressor Discharge temperature sensor error (open/short)
E320 Compressor OLP sensor error (open/short)
Guidance Please, The System turn off and replace sensor which is related.
Contents
Q6 
Check point Remarks
Analysis
Outdoor unit fails to search indoor units or to check
indoor address.
The pipe checking operation
Step 1

each other, check to connecting.
Pipe connecting
Step 2
Check to indoor unit’s sensor being connected in
proper location.
EEV Coil
Step 3
Check to indoor unit’s sensor being connected in proper
location.
Indoor sensor
Guidance
During the pipe checking operation , system check temperature change of indoor Heat exchanger.
In case, indoor sensor defect, EEV coil connector detach, malfunction of EEV, Leakage of Refrigerant,
and etc can make this case.