135
10. Installation
Module installation
<Case 3>
Over 500Over 500 Over 600
Over 100 Over 100
Over 100
Over 100
Over 100
Over 100 Over 100 Over 100
Front side
Front side
<Case 1>
<Case 2>
Over 200
Over 100
Over 300
(S2)
Over 500
(S1)
Over 100
Over 100
Over 100
Over 300
Over 400Over 400
Height of
the wall is
unlimited
Front
side
Front side
For <Case 1> or <Case 3>
• Height of the wall on the front side should not be
higher than 1500mm.
• Height of the wall on the air inlet side should not be
higher than 500mm.
• Height of the wall on the side is not limited.
• If the height of the wall exceeds by certain value (h1, h2),
additional clearance [(h1)/2, (h2)/2 : Half of the exceeded
distance] should be added to the service space (S1, S2).
1500 h1
500 h2
Front side
(Unit : mm)
S1+h1/2 S2+h2/2
At Machinery Room
• Make sure to install both discharge duct and suction
grille / louver
• Static pressure of the discharge duct should be within
the standard specification (78.45Pa) when installing
the duct.
• Secure enough cross-sectional area on grille
surface for easy air intake in case of machinery room
installation.
Over 200
Over 500
Discharged air
Grille/louver
Discharged air
Grille/louver
Over 500
Over 200
Suction air
Ex.) Mechanical room