Product Specifications(cont.)
■ RHF100EE
Power Source AC220V, 60Hz
Ventilation Mode Heat-Ex Ventilation By-Pass Ventilation
The Level of the Air Volume Turbo High Low Turbo High Low
Power Supply(W) 460 380 320 460 380 320
Air Volume(m³/h) 1,000 800 670 1,000 800 670
External Static Pressure(mmAq) 18.5 13.2 9.1 18.5 13.2 9.1
Temperature Exchange
Efficiency(%)
Cooling 68 69 70
- - -
Heating 80 81 83
- - -
Valid Heat Exchange
Efficiency(%)
Cooling 50 53 55
- - -
Heating 72 74 77
- - -
Size(widthxheightxdepth)(mm) 1,220×340×1,135
Weight(kg) 67
Duct Size(mm) 250
Air Volume Control Specifications (Turbo) Range : External Static Pressure 7.5~18.5[mmAq], Power Supply 270.0~460.0[W]
Trial Operation Conditions
1. Air Volume/ External Static Pressure, Comply with KS Heat Exhaust Ventilation System Standards(KS B6879).
2. Heat Exchange/Temperature Exchange Efficiency, Comply with regulations to pro
-
mote high efficiency energy devices,
[Cooling], Indoor(24˚C DB/17˚C WB), Outdoor(35˚C DB/24˚C WB)
[Heating], Indoor(22˚C DB/13.9˚C WB), Outdoor(2˚C DB/0.44˚C WB)
3. Duct length refers to its size when friction loss coefficient stands at 0.02
2-4
27723A(1)_RHF-025EB_1.indd 7 2007-05-09 ソタネト 4:23:01