2-2 Product Specifications
Power Source AC220V, 60Hz
Ventilation Mode Heat-Ex Ventilation By-Pass Ventilation
The Level of the Air Volume Turbo High Low Turbo High Low
Power Supply(W) 120 105 85 120 105 85
Air Volume(m³/h) 250 210 180 250 210 180
External Static Pressure(mmAq) 12.2 9.2 6.2 12.2 9.2 6.2
Temperature Exchange
Efficiency(%)
Cooling 69 71 73
- - -
Heating 81 83 85
- - -
Valid Heat Exchange
Efficiency(%)
Cooling 52 55 59
- - -
Heating 72 74 77
- - -
Size(widthxheightxdepth)(mm) 660 x 350 x 600
Weight(kg) 25.5
Duct Size(mm) 150
Air Volume Control Specifications (Turbo) Range : External Static Pressure 5.0~12.2[mmAq], Power Supply 85.0~120.0[W]
Trial Operation Conditions
1. Air Volume/ External Static Pressure, Comply with KS Heat Exhaust Ventilation System Standards(KS B6879).
2. Heat Exchange/Temperature Exchange Efficiency, Comply with regulations to pro
-
mote high efficiency energy devices,
[Cooling], Indoor(24˚C DB/17˚C WB), Outdoor(35˚C DB/24˚C WB)
[Heating], Indoor(22˚C DB/13.9˚C WB), Outdoor(2˚C DB/0.44˚C WB)
3. Duct length refers to its size when friction loss coefficient stands at 0.02
■ RHF025EE
Power Source AC220V, 60Hz
Ventilation Mode Heat-Ex Ventilation By-Pass Ventilation
The Level of the Air Volume Turbo High Low Turbo High Low
Power Supply(W) 115 100 85 115 100 85
Air Volume(m³/h) 350 300 260 350 300 260
External Static Pressure(mmAq) 17.0 12.1 9.0 17.0 12.1 9.0
Temperature Exchange
Efficiency(%)
Cooling 71 73 75
- - -
Heating 80 82 84
- - -
Valid Heat Exchange
Efficiency(%)
Cooling 54 57 60
- - -
Heating 71 74 77
- - -
Size(widthxheightxdepth)(mm) 1,012x270x1,000
Weight(kg) 42.5
Duct Size(mm) 200
Air Volume Control Specifications (Turbo) Range : External Static Pressure 4.0~17.0[mmAq], Power Supply 68.0~115.0[W]
Trial Operation Conditions
1. Air Volume/ External Static Pressure, Comply with KS Heat Exhaust Ventilation System Standards(KS B6879).
2. Heat Exchange/Temperature Exchange Efficiency, Comply with regulations to pro
-
mote high efficiency energy devices,
[Cooling], Indoor(24˚C DB/17˚C WB), Outdoor(35˚C DB/24˚C WB)
[Heating], Indoor(22˚C DB/13.9˚C WB), Outdoor(2˚C DB/0.44˚C WB)
3. Duct length refers to its size when friction loss coefficient stands at 0.02