3-4
Alignment and Adjustments
MAIN
7-Segment
Inverter LED
Content Measures
Product operation status in
case of error
Yellow Green Red
Number of
Times
Outdoor unit
compressor/
outdoor unit
fan
Comp Vlimit error
Check the connection status of compressor
Check the resistance between different phases
in compressor
9 Times Operation-off
DC-Link voltage under/
over error
Check the connection of input power
-
Restart(after
3min.)
Comp rotation error
Check the connection status of the compressor
Check the resistance between different phases
in compressor
3 Times Operation-off
Current sensor error
Check the PCB operates normally
1 Time Operation-off
DC-Link valtage sensor error
Check the connection of input power
1 Time Operation-off
OTP error
Check the PCB operates normally
1 Time Operation-off
AC Line Zero Cross Signal
out
Check the connection of input power
1 Time Operation-off
Comp Lock error
Check the connection status of the compressor
Check the resistance between different phases
in compressor
3 Times Operation-off
Fan error(two fan outdoor)
Check the input power connection status
Check the connection status between the
motor and PCB in outdoor unit
Check the fuse of indoor/outdoor units
1 Time Operation-off
GAS Leak error(Dual/Single)
Check refrigerant is filled
Check the indoor EVA sensor
3 Times Operation-off
Capacity miss match
Check the indoor unit's option code
Check the capacity of indoor unit's and
outdoor unit's
1 Time Operation-off
-
Test Operation at Cooling
Mode
- - -
-
Test Operation at Heating
Mode
- - -
Outdoor Error Display and Check Method(cont.)