EasyManua.ls Logo

Samsung MCU Series - Wiring Works; Circuit Breaker and Wire Installation; Wiring Diagrams and Connections

Samsung MCU Series
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16
Installing the circuit breaker and wires
Power supply MCCB ELB Power cable Earth cable Communication cable
Max : 242V
Min : 198V
X A
XA, 30mmA
0.1 sec
0.0039inch
2
(2.5mm
2
)
0.0039inch
2
(2.5mm
2
)
0.0012~0.0023inch
2
(0.75~1.5mm
2
)
Installing the wire
X
Supply the 220-240V/208-230V power to L1, L2 (L, N) of MCU separately
X
Connect the communication cable from the outdoor unit to F1, F2 of MCU.
X
Power Line and communication line must be connected as shown in drawing.
Case 1 Case 2
220-240V/208-230V / Single Phase
(Supply separately)
ELB
MCCB
Outdoor
Unit
Indoor
Unit
Indoor
Unit
ELB
MCCB
Outdoor
Unit
Indoor
Unit
Indoor
Unit
MCU
Indoor
Unit
220-240V/208-230V / Single Phase
(Supply separately)
Case 3
ELB
MCCB
Outdoor
Unit
Indoor
Unit
MCU
Indoor
Unit
Indoor
Unit
220-240V/208-230V / Single Phase
(Supply separately)
X
Power Line and communication line must be installed as shown in drawing
Hole size is Φ 43.7 mm
MCU MCU
Indoor Unit
Hole for MCU main power supply
Hole for communication
Refrigerant piping works