EasyManua.ls Logo

Samsung MH035FMEA - 4. Troubleshooting; 4-1 Display Error and Check Method

Samsung MH035FMEA
204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Samsung Electronics 4-1
4. Troubleshooting
4-1 Display Error and Check Method
4-1-1
Indoor unit
Communication error (unable to receive data) Communication cable connection
Communication error (outdoor cannot communicate) Another indoor unit or indoor PCB
Indoor unit room temperature sensor error (Open/Short) Room temperature sensor, indoor PCB
Indoor unit heat exchanger in temperature sensor error
Heat exchanger in sensor, indoor PCB
(Open/Short)
Indoor unit heat exchanger out temperature sensor error
Heat exchanger out sensor, indoor PCB
(Open/Short)
Indoor unit heat exchanger in temperature sensor detached Heat exchanger in sensor
Indoor unit heat exchanger out temperature sensor detached Heat exchanger out sensor
Indoor unit heat exchanger in & out temperature sensor
Heat exchanger in & out sensor
detached
Indoor unit float switch second detection -
Indoor unit fan motor malfunction Fan motor and cable
More than 2 indoor units cool and heat simultaneously Another indoor unit operation mode
EEPROM error Indoor PCB
Option code setting error Option code
Cable miss-wiring Cable connection (Indoor & Outdoor unit)
MPI error malfunction MPI
The number of indoor unit mismatched
Cable connection (another indoor unit &
outdoor unit), SW01(outdoor)
Compressor discharge sensor error(Short/Open) Outdoor unit
Outdoor unit error Outdoor unit (Error code)
Main checking Point / Remark
Display
Explanation
MH FVEA/MH FBEA/MH FAEA

Related product manuals