E-8
PREPARING THE INSTALLATION
Deciding on Where to Install the Air Conditioner (Continued)
MH070FX
A4B / MH080FX
A4B
Indoor unit Outdoor unit
Power supply
Ø, V, Hz

020/023/026/030/035/052

MH070FX
A4B
MH080FX
A4B
1,220-240, 50
Unit
Outside diameter
Liquid Gas

020/023/026/030/035

1/4" 3/8"

052

1/4" 1/2"
Piping outside diameter
(h) (H)
A
B
1 Room max
length
4 Room total max
length
Max height between
indoor unit & outdoor unit
Max height between
indoor units
Dimension 25m 70 m 15m 7.5 m
Composition A,B,C,D A+B+C+D (H) (h)
Piping length and the height
C D
200 mm
or more
160 mm
or more
100 mm
or more
Main power switch
600 mm
minimum
300 mm
minimum
300 mm
minimum
600 mm
minimum
CAUTION:
3 m as minimum pipe length: It will
reduce noise and vibration.
This value must be increased at 7.5
meters in case it is connected just one
indoor unit.
System can work with one indoor unit connected, but it is recommended that the TOTAL number
of indoor unit suggested by manufacturer are connected to obtain the maximum performance.
The appearance of the unit may be different from the diagram depending on the model.
Make at least one round:
It will reduce noise and vibration
08'FJM_OUTDOOR_28896A_IM_E.indd 8 2007-12-12 14:28:11