9) Network variable
(1) Indoor unit/ ERV/ AHU kit object
No. Name Type M/O Description
1 nviONOff SNVT_switch O ON/OFF command
2 NviApplicMode SNVT_hvac_mode O Setting operating mode
3 nviSetpoint SNVT_temp_p O Setting desire temperature
4 nviFanStatus SNVT_switch O Setting fan speed
5 nviERVMode SNVT_count O Setting ERV operation mode
6 nviFilterReset SNVT_switch O Filter reset command
7 nviUserLockout SNVT_switch O Setting the restriction of remote control use
8 nviOccOpMode SNVT_switch O Setting cooling only mode / heating only mode
9 nviCoolTempLock SNVT_switch O Setting the low temperature limit
10 nviHeatTempLock SNVT_switch O Setting the high temperature limit
11 nvoSpaceTemp SNVT_temp_p M Display indoor temperature
12 nvoApplicMode SNVT_hvac_mode O Display operating mode
13 nvoSetpoint SNVT_temp_p O Display desire temperature
14 nvoOnOff SNVT_switch O Display ON/OFF status
15 nvoFanStatus SNVT_switch O Display fan speed
16 nvoERVMode SNVT_count O Display ERV operating mode
17 nvoErrorCode SNVT_count O Display Error code
18 nvoDeviceAlarm SNVT_state O
Remote control lock, Filter sign, Thermo ON/OFF,
Error occurrence status display
19 nvoOccOpMode SNVT_switch O Cooling only/Heating only setup status display
20 nvoCoolTempLock SNVT_switch O Display low temperature limit setting status
21 nvoHeatTempLock SNVT_switch O Display high temperature limit setting status
22 nvoUserLockout SNVT_switch O Display the restriction of remote control use
23 nvoEnergyConp SNVT_elec_kwh_l O %JTQMBZFMFDUSJDJUZVTBHF5JNF1FSJPE
24 nvoEnergyCon SNVT_elec_kwh_l O Display electricity usage (Basic date)
25 nvoRuntimep SNVT_time_hour O %JTQMBZVTFEIPVST1FSJPE
26 nvoRuntime SNVT_time_hour O Display used hours (Basic date)
27 nvoDevListDesc SNVT_str_asc O Indoor unit HW information
No. Name Type M/O Description
1 nviDigitalOut[6] SNVT_ switch O
Control Digital output of DMS
2 nviAllOff SNVT_hvac_emerg O
Control all indoor unit / ERV OFF
3 nvoDigitalOut[6] SNVT_ switch O
Display Digital output status of DMS
4 nvoDigitalIn[8] SNVT_ switch O
Display Digital input status of DMS
5 nvoSystemLock SNVT_ switch O
Display System Lock status of DMS
6 nvoDMS2Alarm SNVT_ count O
Display communication error of the sub device
connected to DMS
7 nvoSystemAlarm SNVT_ count O
Display error satus
No. Name Type M/O Description
1 nciSndHrtBt
SNVT_time_sec
4$15NBY4FOE5JNF
O Send Heartbeat
2 nciMinOutTm
SNVT_time_sec
4$15NJO4FOE5JNF
O Minimum Send Time
3 nciMinDeltaTemp
SNVT_temp_p
4$15NJO%FMUB5FNQ
O Min. difference before update
4 nciDelayStatrup
SNVT_time_sec
4$15QXSVQ%FMBZ
O Delay time after a power-up