12
OH75A/OH75F/OH85F
• Clearance ( ): 400 mm or more
• Air inlet ( , , )
Total open area of the ventilation holes: 126000 mm or more
Ventilation opening ratio (% of total opening): 50 % or more
• Air outlet ( , )
Total open area of the ventilation holes: 114000 mm or more
Ventilation opening ratio (% of total opening): 50 % or more
"
Add partitions without any gap to completely separate the inlet and outlet.
– Secure at least 400 mm of clearance between two products.
"
The structure of the enclosure must be designed to clean the inlet / outlet / heat exchanger
regularly.
Ex) Add a door for workers to ensure access for cleaning with the tools.
– For details, see Cleaning and cautions.
"
Ensure the minimum clearance between inlet and outlet of the enclosure.
• Minimum separation distance for each model( )
Model name Minimum clearance( )
OH75A/OH75F
380 mm
OH85F
Example 1
At least 400 mm of clearance
between products
Partition
Partition
Back Side view