Single enclosure unit
Design the outdoor unit according to the following specications to keep discharged hot air from owing back
into the inlet.
OH46F/OH55A/OH55F
Air inlet( )
Total open area of the ventilation holes: 53000 mm⁲ or more
Ventilation opening ratio (% of total opening): 50 % or more
Air outlet( , )
Total open area of the ventilation holes ( ): 29000 mm⁲ or more
Total open area of the ventilation holes (
): 29000 mm⁲ or more
Ventilation opening ratio (% of total opening): 50 % or more
"
Design the locations of the enclosure unit inlet and outlet to match the locations of the
outdoor unit inlet and outlet.
"
Ensure the minimum clearance between inlet and outlet of the enclosure.
Minimum separation distance for each model ( )
Model name Minimum clearance( )
OH46F 235 mm
OH55A/OH55F 286 mm
Example 1
Back Side view
Example 2
Back Side view