OH75A/OH75F/OH85F
• Air inlet( )
Total open area of the ventilation holes: 63000 mm or more
Ventilation opening ratio (% of total opening): 50 % or more
• Air outlet( )
Total open area of the ventilation holes: 57000 mm or more
Ventilation opening ratio (% of total opening): 50 % or more
"
Design the locations of the enclosure unit inlet and outlet to match the locations of the
outdoor unit inlet and outlet.
"
Ensure the minimum clearance between inlet and outlet of the enclosure.
• Minimum separation distance for each model ( )
Model name Minimum clearance( )
OH75A/OH75F 380 mm
OH85F 380 mm
Back Side view